Conduit Fill Calculator

Fill % · Jam Ratio · Minimum Size

Calculate the fill percentage of a conduit given one or more cable sizes and quantities. A common rule of thumb is to keep total cable fill at or below 40% for three or more cables, allowing room for cable installation and heat dissipation. This calculator also checks for jam ratio risk — a condition where exactly three similarly-sized round cables can wedge inside a conduit during pulling.

CALCULATOR

Conduit Fill

CONDUIT FILL
17.28
%
CABLE AREA
84.8
mm²
REMAINING
406.1
mm²
Suggested minimum conduit for ≤40% fill: 20mm

Results for guidance only. Verify against current standards and manufacturer data.
Not a substitute for engineering judgement or a licensed professional.

Methodology

Fill percentage is calculated as the total cross-sectional area of all cables divided by the internal cross-sectional area of the conduit. Jam ratio (conduit ID ÷ largest cable OD) is checked when exactly three cables are present — ratios between approximately 2.7 and 3.2 create a mechanical wedging risk during cable pulling, since three round objects of similar size can lock together inside a circular conduit.

Assumptions & Limitations

  • Assumes round cables — does not account for flat or irregular cable profiles
  • 40% fill guidance is a general rule of thumb — verify against manufacturer conduit fill tables and AS/NZS 3000 requirements for your specific installation
  • Does not replace manufacturer pulling tension or bend radius guidance