Primary/Secondary Current · Fault Level (kA / MVA)
Calculate primary and secondary full-load current, transformation ratio, and prospective fault current for a distribution transformer. Fault level can be calculated assuming an infinite source bus (simplified, transformer-only impedance) or including upstream source fault level for a more realistic result. Commonly used for switchgear rating verification and protection coordination studies.
Results for guidance only. Verify against current standards and manufacturer data.
Not a substitute for engineering judgement or a licensed professional.
Transformer full-load current is calculated from kVA rating and voltage: . The simplified "infinite bus" fault current assumes an infinitely stiff upstream source and calculates fault current purely from transformer impedance: Isc = I_rated / (%Z/100). Including source impedance uses a per-unit calculation combining transformer and source impedance on a common base, giving a more realistic (lower) fault current.
A 500kVA, 11000/415V transformer with 5% impedance: secondary FLC = . Infinite-bus fault current = 696 / 0.05 = 13,919A ≈ 13.9kA, or 10.0 MVA fault level.